2 electrical data 230v, Electrical data 230v, 7 technical data – NORD Drivesystems BU0500 User Manual

Page 151

Advertising
background image

7 Technical data

BU 0500 GB-1013

151

7.2.2 Electrical data 230V

FI type (size 1):

SK 5xxE…

-250-323-A

-370-323-A

-550-323-A

-750-323-A

Nominal motor power

(4-pole standard motor)

230V

0.25hp

0.37 kW

0.55 kW

0.75hp

240V

1

/

3

hp

½ hp

¾ hp

1 hp

Input

Mains voltage

1~ /3~ 230V

1 / 3 AC 200 … 240V,

± 10%, 47 … 63Hz

Input current

1~ /3~ rms

3.7 A / 2.4 A

4.8 A / 3.1 A

6.5 A / 4.2 A

8.7 A / 5.6 A

1~ /3~ FLA

3.7 A / 2.4 A

4.8 A / 3.1 A

6.4 A / 4.1 A

8.6 A / 5.5 A

Recommended
mains fuse*

1~ /3~ 1 AC slow-

acting

6 A / 6 A

6 A / 6 A

10 A / 10 A

15 A / 10 A

CB

5 A / 5 A

5 A / 5 A

10 A / 10 A

10 A / 10 A

Permissible mains
fuses for UL*

Fuse, 300V

6 A / 6 A

6 A / 6 A

10 A / 10 A

25 A / 10 A

Bussmann

FRS-R-6

FRS-R-6

FRS-R-10

FRS-R-15 /-10

CB

5 A / 5 A

5 A / 5 A

10 A / 10 A

10 A / 10 A

O

ut

put

Output voltage

3~ 230V

3 AC 0 - Mains voltage

Output current

rms

1.7 A

2.2 A

3.0 A

4.0 A

FLA

1.7 A

2.2 A

2.9 A

3.9 A

Min. braking resistor

Accessories

240

W

190

W

140

W

100

W

Type of ventilation

Free convection

Weight

Approx. [kg]

1.4

* see also Section 1.5.2. Fuses: High-Interrupting Capacity, Current Limiting Classes (z.B. R, J, …), circuit breaker (CB): Inverse Time Trip Type

FI type (size 2/ 3):

SK 5xxE…

-111-323-A

-151-323-A

-221-323-A

-301-323-A

-401-323-A

Nominal motor power

(4-pole standard motor)

230V

1.1 kW

1.5 kW

2.2 kW

3.0 kW

4.0 kW

240V

1½ hp

2 hp

3 hp

4 hp

5 hp

Input

Mains voltage

1~ /3~ 230V

1 / 3 AC

200 … 240V,

± 10%, 47 … 63Hz

3 AC

200 … 240V,

± 10%, 47 … 63Hz

Input current

1~ /3~ rms 12.0 A / 7.7 A 15.2 A / 9.8 A 19.6 A/ 13.3 A

- / 17.5 A

- / 22.4 A

1~ /3~ FLA 11.9 A / 7.6 A 15.0 A / 9.7 A 19.4 A/ 13.1 A

- / 17.2 A

- / 22.0 A

Recommended
mains fuse*

1~ /3~ 1 AC slow-

acting

15 A / 10 A

20 A / 10 A

25 A / 20 A

- / 20 A

- / 25 A

CB

- / 10 A

- / 10 A

- / -

- / 20 A

- / 25 A

Permissible mains
fuses for UL*

Fuse, 300V

30 A / 10 A

30 A / 10 A

30 A / 30 A

- / 30 A

- / 30 A

Bussmann FRS-R-15 /-10 FRS-R-20 /-10 FRS-R-25 /-20

- / FRS-R-20

- / FRS-R-25

CB

- / 10 A

- / 10 A

- / -

- / 25 A

- / 25 A

O

ut

put

Output voltage

3~ 230V

3 AC 0 - Mains voltage

Output current

rms

5.5 A

7.0 A

9.5 A

12.5 A

16.0 A

FLA

5.4 A

6.9 A

9.3 A**

12.3 A

15.7 A

Min. braking resistor

Accessories

75

W

62

W

46

W

35

W

26

W

Type of ventilation

Fan cooling, temperature-controlled Switching thresholds:

ON= 57°C OFF=47°C

Weight

Approx. [kg]

1.8

2.7

* see also Section 1.5.2. Fuses: High-Interrupting Capacity, Current Limiting Classes (z.B. R, J, …), circuit breaker (CB): Inverse Time Trip Type

** for single-phase mains supply of SK 5xxE

-

221

-

323

-

A: FLA Output = 8.8 A