Enclosure management commands 120

•

Description:

o

Turns power savings mode on or off. Enabling power savings (specify ON) turns unneeded power

supplies off. (In the Onboard Administrator GUI, you turn power savings mode on or off using the

Enable Dynamic Power setting from the Power Management screen.)

o

The increased load on the remaining power supplies increases their efficiency, resulting in less
power consumption.

o

The default is OFF.

•

Access level/Bay level:
OA administrator, OA operator

•

Restrictions:
Power savings is supported with all c3000 power supplies. It supports c7000 power supplies only if
operating with high-line input voltage (such as 220V AC). It is not supported with c7000 -48V DC

power supplies.

SET TIMEZONE

•

Command:
SET TIMEZONE "<timezone>"

•

Description:
Sets the time zone
See Time zone settings (on page

208

) for appropriate time zones. Some that are commonly used

include: CET, CST6CDT, EET, EST, EST5EDT, GB, GMT, HST, MET, MST, MST7MDT, NZ, PRC,

PST8PDT, UCT, and UTC.

•

Access level/Bay level
OA administrator, OA operator

•

Restrictions:
None

SHOW CONFIG

•

Command:
SHOW CONFIG

•

Description:
Displays the script required to recreate the settings of the enclosure. Passwords are not included for any

user.

•

Access level/Bay level:
OA administrator

•

Restrictions:
None

•

Example:

OA-0018FE27577F> SHOW CONFIG

#Script Generated by Administrator