Show enclosure power_cap, Show enclosure power_cap_bays_to_exclude – HP Onboard Administrator User Manual

Page 203

Advertising
background image

Enclosure Dynamic Power Cap commands 203

If you have previously specified bays to exclude, using this command again replaces that specification

rather than augmenting it.

Access level/Bay level:
OA administrator, OA operator

Restriction:
You can exclude no more than one fourth of the bays.

SHOW ENCLOSURE POWER_CAP

Command:
SHOW ENCLOSURE POWER_CAP

Description:
Displays the current Enclosure Dynamic Power Cap in watts.

Access level/Bay level:
All

Restriction:
None

Example:

OA-0018FE27577> SHOW ENCLOSURE POWER_CAP

Enclosure Dynamic Power Cap:

Disabled

Derated Circuit Capacity:

Disabled

Rated Circuit Capacity:

Disabled

Allowable Enclosure Dynamic Power Cap:

3123 - 7676 Watts AC

Allowable Derated Circuit Capacity:

3123 - 7676 Watts AC

Allowable Rated Circuit Capacity:

3428 - 7676 Watts AC

SHOW ENCLOSURE
POWER_CAP_BAYS_TO_EXCLUDE

Command:
SHOW ENCLOSURE POWER_CAP_BAYS_TO_EXCLUDE

Description:
Displays the bays in the enclosure that are exempt from the Enclosure Dynamic Power Cap.

Access level/Bay level:
All

Restriction:
None

Example:

OA-0018FE27577F> show enclosure power_cap_bays_to_exclude

Bays opted out: None