SECTION 6 - JLG CONTROL SYSTEM

3121265

– JLG Lift –

6-19

GEN SET/WELDER:
10

0

1

2

NO: No generator installed.

BELT DRIVE: Belt driven setup.

HYDRAULIC DRIVE: Hydraulic driven setup.

1

GEN SET CUTOUT:
11*

0

1

MOTION ENABLED: Motion enabled when generator is ON.

MOTION CUTOUT: Motion cutout in platform mode only.

0

* Only visible if Gen Set / Welder Menu selection is not 0.

H & T LIGHTS:
12

0

1

NO: No head and tail lights installed.

YES: Head and tail lights installed.

0

LOAD SYSTEM:
13*

0

1

2

3

4

NO: No load sensor installed.

WARN ONLY: Functions in creep, overload lamp lit, platform alarm beeps (5 sec ON,
2 sec OFF).

CUTOUT PLATFORM: All functions cutout, overload lamp lit, platform alarm beeps (5
sec ON, 2 sec OFF).

CUTOUT ALL: All functions cutout, flash overload light (500mS on, 500mS off), plat-
form alarm beeps (5 sec ON, 2 sec OFF).

SPECIAL 1: Functions in creep, overload lamp lit, disables main telescope out & main
lift up, platform alarm beeps (5 sec ON, 2 sec OFF).

0

* Only visible under certain market selections.

* Certain market selections will limit load system options or alter default setting.

Table 6-2. Machine Configuration Programming Information - Version P7.X to Present

Configuration Digit

Number

Description

Default

Number