SECTION 6 - JLG CONTROL SYSTEM

3121265

– JLG Lift –

6-129

Table 6-13. Load Moment Pin Troubleshooting: Moment Pin Sensor Fault

STEP

FAULT CODE/SYMPTOM

REPAIR

YES

NO

1

8/6 MOMENT PIN SENSOR FAULT The moment
pin has reported a fault flag

Use the Analyzer, scroll to the
DIAGNOSTICS menu, press
ENTER, then scroll to the
MOMENT menu, and press
ENTER, check to see if PIN E
FLAGS has any numbers on the
screen display.

Replace load moment pin
& Perform the Boom Sen-
sor calibration process

Contact JLG Service
Dept.

Table 6-14. Load Moment Pin Troubleshooting: New Moment Pin Detected Fault

STEP

FAULT CODE/SYMPTOM

REPAIR

YES

NO

1

8/6 NEW MOMENT PIN DETECTED FAULT A
moment pin was detected on the system different
from the one used to calibrate the machine.

Perform the Boom Sensor cali-
bration process to accept the
new load moment pin.

Verify BCS check and
review all faults prior to
contacting JLG Service
Dept.

Contact JLG Service
Dept.