Boom sensor calibration position 9 -76 – JLG 1100SB Service Manual User Manual

Page 360

Advertising
background image

SECTION 6 - JLG CONTROL SYSTEM

6-76

– JLG Lift –

3121265

Press Enter. The screen will read:

31.

Telescope to the yellow witness mark (controller will
be close - operator must position the pointer to cen-
ter line on decal within 0.25" [6 mm]) for Calibration
Position 9.

When the boom is in the proper position, hit Enter.
The screen will read:

When Position 9 calibrating is complete, the screen
will read:

Figure 6-22. Boom Sensor Calibration Position 9