If a task overflow leads to a system error

If, for instance, a continuous loop or too much program content has been programmed for a task
and the task cannot process the program within the specified interval time, a system error will occur
in the automation system.

System errors can also occur when a running task is interrupted so frequently by other tasks that
the program cannot be processed within the specified task runtime.

A system error trips the automation system.

The response of motor control and digital outputs can be set under
Project

Exception handling.

(also refer associated system organization unit description in the manual for the respective
Lenze automation system.)

The program can only be restarted after a TRIP reset or mains switching.

A TRIP reset (Keypad: STOP

àRUN key; GDC: Code C0043) resets the Lenze automation system

after a task overflow, and the error message “ Task overflow” is acknowledged.The automation
system must be corrected to prevent further task overflows.

The watchdog time is set as follows:

Use the task dialog box Properties, input field Watchdog time to enter the maximum runtime
for the task.

Interval: The watchdog time is between 0-100 % of the interval time (default=90 % ) and can
be set between 1 ms and 300 ms.
(With a 1 ms task, the watchdog time is 1 ms = 100 % fixed.)

Event/Interrupt: The watchdog time can only be set less than 300 ms (default=100 ms).

Use the dialog box

Exception handling (Project

WException handling), input field

Watchdog time to enter the maximum runtime for the cyclical task (PLC_PRG).

Tripping the watchdog time

Tripping the watchdog time activates an error message in the PLC.

This error message is displayed on the Keypad/in GDC in code C0168.

After TRIP reset, error message and PLC program will be reset. Use the DDS start command
or C2108=1 to restart the program.

8.8.5

Task declaration

A task declaration consists of the task name, the entry for task priority and the condition for its
execution.

The condition can be a time interval (1 ms to 16 s) after which the task is to be executed, an event
(rising edge at the digital input or FALSE/TRUE change of a global variable) or a hardware interrupt.

Every task can now be assigned a list of programs (Program-type POUs) to be called by the task.
These programs are processed in the listed order.

Tip!

The task settings (properties) cannot be changed in online mode!