Drive plc developer studio, Appendix, Show/hide bookmarks – Lenze DDS v2.3 User Manual

Page 326

Advertising
background image

Drive PLC Developer Studio

Appendix

15-16

l

DDS EN 2.3

No.

Possible remedy

Cause

4061

VAR_IN_OUT parameter <Name> of <Name> must be
assigned.

Write-accessible variables must be assigned to VAR_IN_OUT parameters as these can be
modified within the organization unit.

4062

No external access to VAR_IN_OUT parameter <Name> of
<Name>.

VAR_IN_OUT parameters must only be written or read within the organization unit (reference
transfer).

4063

VAR_IN_OUT parameter <Name> of <Name> cannot be
assigned bit addresses.

A bit address is no valid physical address.
Transfer a variable or a direct non-bit address.

4064

VAR_IN_OUT must not be overwritten in local action call !

Delete the assignment of the VAR_IN_OUT variables for the local action call.

4070

Too deeply nested expression in organization unit.

Reduce the nesting depth by distributing the expression across several expressions with the
help of assignments to intermediate variables.

4071

Network too large

Divide the network into several networks.

4100

^ requires a pointer type

You are attempting to dereference a variable that has not been declared as POINTER TO.

4110

[<index>] only allowed for array variables

You are using [<index>] for a variable that has not been declared as ARRAY OF.

4111

The expression in the index of an array must have an
INT-type result.

Use an expression of the respective type, or a type conversion.

4112

Too many array indices

Check the number of indices (1, 2, or 3) for which the array has been declared, and remove
the superfluous indices.

4113

Insufficient array indices

Check the number of indices (1, 2, or 3) for which the array has been declared, and add the
missing indices.

4114

Constant index outside array boundaries

Ensure that the applied indices range within the array boundaries.

4120

A ”

.

” must be preceded by a structure variable.

The identifier to the left of the period must be a STRUCT or FUNCTION_BLOCK-type variable
or the name of a FUNCTION or a PROGRAM.

4121

<Name> is no component of <Object name>.

The component <Name> is not included in the definition of object <Object name>.

4122

<Name> is not an input parameter of the called function
block.

Check the input variables of the called function block, and change <Name> into one of these
variables.

4200

LD expected

Add at least one LD instruction in the editor window of the IL organization unit or behind the
jump label.

4201

IL operator expected

Every IL instruction must start with an operator or a jump label.

4202

Unexpected end of the subexpression

Insert the right parenthesis.

4203

<Name> in parentheses not allowed

The specified operator is not permitted within an IL subexpression.
(impermissible are: JMP, RET, CAL, LDN, LD, TIME)

4204

Right parenthesis without left parenthesis.

Insert left parenthesis, or delete right parenthesis.

4205

No comma permitted after )

Remove the comma behind the right parenthesis.

4206

No jump labels in subexpressions.

Move the jump label outside the subexpression.

4207

N modifier requires a BOOL, BYTE, WORD or DWORD-type
operand.

The N modifier requires a data type for which a Boolean negation can be performed.

4208

The expression in front of a conditional command must
return a BOOL-type result

Ensure that the expression returns a Boolean result, or use a type conversion.

4209

Function names are not allowed here.

Replace the function call with a variable or constant.

4210

CAL, CALC and CALN require a function block instance as
an operand

Declare an instance of the function block to be called.

4211

Comments in IL at the end of the line only.

Move the comment to the end of the line or into a separate line.

4212

Accumulator invalid before conditional instruction

The accumulator content is not defined.
This is the case after instructions that do not return any result (CAL, for example).

4213

S and R require a BOOL-type operand

Use a Boolean variable at this position.

4250

No correct start for an ST instruction

The line does not start with a correct ST instruction.

4251

Function <name> has too many parameters.

More parameters were specified than were declared in the function definition.

4252

Function <name> has insufficient parameters.

Fewer parameters were specified than were declared in the function definition.

4253

IF and ELSIF require a Boolean expression as condition

Ensure that the condition following an IF and ELSIF is a Boolean expression.

4254

WHILE requires a Boolean expression as condition

Ensure that the condition following a WHILE is a Boolean expression.

4255

UNTIL requires a Boolean expression as condition

Ensure that the condition following an UNTIL is a Boolean expression.

4256

NOT requires a Boolean operand.

Ensure that the condition following a NOT is a Boolean expression.

4257

The counter of the FOR instruction must be INT-type

Ensure that the counter variable is an integer or bitstring data type (DINT, DWORD, for
example).

4258

The counter in the FOR instruction is no write-accessible
variable

Replace the counter variable with a write-accessible variable.

4259

The start value of the FOR instruction must be INT-type.

The start value of the FOR instruction must be compatible with the counter variable type.

4260

The end value of the FOR instruction must be INT-type.

The end value of the FOR instruction must be compatible with the counter variable type.

4261

The incrementation value of the FOR instruction must be
INT-type.

The incrementation value of the FOR instruction must be compatible with the counter
variable type.

4262

EXIT is permitted only within a loop.

Use EXIT only within FOR, WHILE or UNTIL instructions.

4263

Number, ELSE or END_CASE expected

Only a number or an ELSE instruction, or the end instruction END_CASE, can be specified
within a CASE.

Show/Hide Bookmarks