Drive plc developer studio – Lenze DDS v2.3 User Manual

Page 54

Advertising
background image

Drive PLC Developer Studio

Programming languages

4-16

l

DDS EN 2.3

Example of a declaration

PROGRAM flags
VAR

SFCEnableLinit:BOOL;
SFCError:BOOL;
SFCErrorStep:STRING;
SFCReset AT %IX1.0.2: BOOL;
SFCInit AT %IX1.0.3:BOOL;

END_VAR

SFCQuitError

Processing of the SFC diagram will be suspended for as long as this Boolean variable remains TRUE.
Timeouts in variables SFCError will be reset. All previous times in the active steps will be reset when
the variable is reset to FALSE.

SFCPause

Processing of the SFC diagram will be suspended for as long as this Boolean variable remains TRUE.

SFCError

This Boolean variable becomes TRUE if a timeout occurred in an SFC diagram. If variable SFCError
is not reset again, and the first timeout is then followed by a second one in the program, the second
one will not be registered.

SFCTrans

This Boolean variable becomes TRUE when a transition switches.

SFCErrorStep

This variable is a STRING-type variable that, if SFCError registers a timeout, stores the name of the
step that causes the timeout.

SFCErrorPOU

This STRING-type variable, after a timeout, contains the name of the organization unit in which the
timeout occurred.

SFCCurrentStep

This variable is a STRING-type variable that saves the name of the active step independently of the
watchdog function. In parallel branching, the step is saved in the branch at the extreme right.

SFCTip, SFCTipMode

These BOOL-type variables permit the SFC tip mode. If that is activated via
SFCTipMode

= TRUE, the next step can be reached only if SFCTip is set to TRUE. As long as

SFCTipMode

is set to TRUE, the transitions may also be used for switching.

SFCErrorAnalyzation

This variable is a STRING-type variable. If the SFC flag SFCError registers a timeout,
SFCErrorAnalyzation

outputs the responsible variables or transition expressions.

This function requires the library Analyzation.lib to be integrated into the DDS project.

Note!

On some target systems, the length of the output of variables or transition expressions can be
limited.

In some cases the string routines can only process 20 characters.