Drive PLC Developer Studio

IEC 61131-3 Standard functions

14-18

l

DDS EN 2.3

14.7.3

TOF

Timer off-delay

TOF(IN, PT, Q, ET)

means:

•

IN

and PT are input variables of type BOOL or TIME.

•

Q

and ET are output variables of type BOOL or TIME.

•

As soon as IN is FALSE, ET will count the time in milliseconds until the value equals that in
PT

and then remain the same.

•

Q

is FALSE if IN is FALSE and ET equals PT. Otherwise Q returns TRUE.

Q

thus has a falling edge when the time set in milliseconds in PT has expired.

Graphic representation of TOF’s time sequence:

Examples
Declaration:

TOFInst : TOF;

IL

FBD

CAL TOFInst(IN:=VarBOOL1, PT:=T#5s)
LD TOFInst.Q
ST VarBOOL2

ST

TOFInst(IN:=VarBOOL1, PT:=T#5s);
VarBOOL2:=TOFInst.Q;