Drive PLC Developer Studio

IEC 61131-3 Standard functions

14-18

l

DDS EN 2.3

14.7.3

TOF

Timer off-delay

TOF(IN, PT, Q, ET)

means:

IN

and PT are input variables of type BOOL or TIME.

Q

and ET are output variables of type BOOL or TIME.

As soon as IN is FALSE, ET will count the time in milliseconds until the value equals that in
PT

and then remain the same.

Q

is FALSE if IN is FALSE and ET equals PT. Otherwise Q returns TRUE.

Q

thus has a falling edge when the time set in milliseconds in PT has expired.

Graphic representation of TOF’s time sequence:

Examples
Declaration:

TOFInst : TOF;

IL

FBD

CAL TOFInst(IN:=VarBOOL1, PT:=T#5s)
LD TOFInst.Q
ST VarBOOL2

ST

TOFInst(IN:=VarBOOL1, PT:=T#5s);
VarBOOL2:=TOFInst.Q;