TOF
Timer off-delay
TOF(IN, PT, Q, ET)
means:
•
IN
and PT are input variables of type BOOL or TIME.
•
Q
and ET are output variables of type BOOL or TIME.
•
As soon as IN is FALSE, ET will count the time in milliseconds until the value equals that in
PT
and then remain the same.
•
Q
is FALSE if IN is FALSE and ET equals PT. Otherwise Q returns TRUE.
Q
thus has a falling edge when the time set in milliseconds in PT has expired.
Graphic representation of TOF’s time sequence:
Examples
Declaration:
TOFInst : TOF;
IL
FBD
CAL TOFInst(IN:=VarBOOL1, PT:=T#5s)
LD TOFInst.Q
ST VarBOOL2
ST
TOFInst(IN:=VarBOOL1, PT:=T#5s);
VarBOOL2:=TOFInst.Q;