Chapter 9

Using the 1756-DHRIO and 1756-DHRIOXT Modules in Remote I/O Applications

Design a Remote I/O Network

Designing a remote I/O network requires applying network and cable design
guidelines.

Network Design Guidelines

Follow these rules as you design a remote I/O network:

All devices connected to a remote I/O network must communicate by
using the same communication rate. The following rates are available for
remote I/O:

57.6kbps

115.2kbps

230.4kbps

Assign unique partial and full racks to each channel used in remote I/O
scanner mode. The channels of a 1756-DHRIO or 1756-DHRIOXT
module cannot scan the same partial or full rack address. For example, to
reduce the possibility of a conflict, you may have channel A communicate
to racks 00…37 octal and channel B communicate to 40…77 octal, or have
channel A communicate to even rack numbers while channel B
communicates to odd rack numbers.

A channel can have a maximum of 32 rack numbers and a maximum of 32
physical devices connected to it.

Cable Design Guidelines

Follow these cable design guidelines in your remote I/O network:

Specify a 1770-CD (Belden 9463) cable for 1756-DHRIO modules.

Specify a Belden 89463 cable for 1756-DHRIOXT modules.

Connect a remote I/O network by using a daisy chain or trunk line/drop
line configuration.

Verify that your system’s design plans specify cable lengths within
allowable measurements.

IMPORTANT

The maximum cable length for remote I/O depends on the transmission
rate. Configure all devices on a remote I/O network to communicate at the
same transmission rate.