Use uncached connections, Maintain pccc message sequences – Rockwell Automation 1756-DHRIO_DHRIOXT ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual

Page 170

Advertising
background image

170

Rockwell Automation Publication 1756-UM514C-EN-P - June 2014

Appendix B

Application Guidelines and Tips

Use Uncached Connections

The following figure illustrates the difference in messages per second available
with uncached connections for each DH+ baud rate.

Maintain PCCC Message
Sequences

The 1756-DHRIO and 1756-DHRIOXT modules do not necessarily send
PCCC messages in the same order in which it receives them. To make sure of
proper sequences, wait for the PCCC response to the initial PCCC message
before you send another PCCC request.