Use Uncached Connections
The following figure illustrates the difference in messages per second available
with uncached connections for each DH+ baud rate.
Maintain PCCC Message
Sequences
The 1756-DHRIO and 1756-DHRIOXT modules do not necessarily send
PCCC messages in the same order in which it receives them. To make sure of
proper sequences, wait for the PCCC response to the initial PCCC message
before you send another PCCC request.