Using the 1756-DHRIO and 1756-DHRIOXT Modules in Remote I/O Applications

Chapter 9

Remote I/O Adapter
Failure Notification

The speed at which the ControlLogix controller is notified that a remote I/O
adapter faulted is directly related to the RPI. The fault, known as a connection
timeout, occurs at four times the RPI. For example, if the RPI is set at 25 ms and a
fault occurs, the ControlLogix controller is not notified for 100 ms.

A remote I/O adapter fault notification occurs whenever the communication
between the remote I/O scanner (Channel A or B) and a remote I/O adapter is
interrupted or the communication between the 1756-DHRIO or
1756-DHRIOXT module and the ControlLogix controller is interrupted.

The Studio 5000 environment alerts you to a rack fault in at least one of the
following ways:

nonzero condition in the

Rack Status tag in the tag editor

fault icon appears in the controller organizer

connections page displays the fault type

Inhibit the Module
Connections

When the inhibit bit is set for the 1756-DHRIO or 1756-DHRIOXT module,
the connection between the ControlLogix controller and the 1756-DHRIO or
1756-DHRIOXT module is terminated.

Although the 1756-DHRIO or 1756-DHRIOXT module connection is
inhibited, the DHRIO scanner (Channel A or B) changes to program mode and
continues to scan the remote I/O adapters on the remote I/O network. When
inhibited, a 1756-DHRIO or 1756-DHRIOXT module accepts configuration
from any ControlLogix controller in the control system.

The 1756-DHRIO or 1756-DHRIOXT module connection can be inhibited
on the module properties connection tab of the Studio 5000 environment.

Inhibit an Remote I/O
Connector Adapter

When the inhibit bit is set for a remote I/O adapter connection, the connection
between the ControlLogix controller and the remote I/O adapter is terminated.

In this case, the 1756-DHRIO or 1756-DHRIOXT scanner (Channel A or B)
continues to scan the remote I/O rack on the remote I/O network and switches
the affected chassis of I/O into program mode. Only the ControlLogix controller
that initiated the configuration of the 1756-DHRIO or 1756-DHRIOXT
module can reestablish communication with the inhibited remote I/O adapter.

RIO rack connections can be inhibited on the module properties connection
dialog box of the Studio 5000 environment.