Using the 1756-DHRIO and 1756-DHRIOXT Modules in Remote I/O Applications
Chapter 9
Remote I/O Adapter 
Failure Notification
The speed at which the ControlLogix controller is notified that a remote I/O 
adapter faulted is directly related to the RPI. The fault, known as a connection 
timeout, occurs at four times the RPI. For example, if the RPI is set at 25 ms and a 
fault occurs, the ControlLogix controller is not notified for 100 ms.
A remote I/O adapter fault notification occurs whenever the communication 
between the remote I/O scanner (Channel A or B) and a remote I/O adapter is 
interrupted or the communication between the 1756-DHRIO or 
1756-DHRIOXT module and the ControlLogix controller is interrupted.
The Studio 5000 environment alerts you to a rack fault in at least one of the 
following ways:
•
nonzero condition in the
Rack Status tag in the tag editor
•
fault icon appears in the controller organizer
•
connections page displays the fault type
Inhibit the Module 
Connections
When the inhibit bit is set for the 1756-DHRIO or 1756-DHRIOXT module, 
the connection between the ControlLogix controller and the 1756-DHRIO or 
1756-DHRIOXT module is terminated.
Although the 1756-DHRIO or 1756-DHRIOXT module connection is 
inhibited, the DHRIO scanner (Channel A or B) changes to program mode and 
continues to scan the remote I/O adapters on the remote I/O network. When 
inhibited, a 1756-DHRIO or 1756-DHRIOXT module accepts configuration 
from any ControlLogix controller in the control system.
The 1756-DHRIO or 1756-DHRIOXT module connection can be inhibited 
on the module properties connection tab of the Studio 5000 environment.
Inhibit an Remote I/O 
Connector Adapter
When the inhibit bit is set for a remote I/O adapter connection, the connection 
between the ControlLogix controller and the remote I/O adapter is terminated.
In this case, the 1756-DHRIO or 1756-DHRIOXT scanner (Channel A or B) 
continues to scan the remote I/O rack on the remote I/O network and switches 
the affected chassis of I/O into program mode. Only the ControlLogix controller 
that initiated the configuration of the 1756-DHRIO or 1756-DHRIOXT 
module can reestablish communication with the inhibited remote I/O adapter.
RIO rack connections can be inhibited on the module properties connection 
dialog box of the Studio 5000 environment.