Reset dh+ diagnostic counters – Rockwell Automation 1756-DHRIO_DHRIOXT ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual

Page 161

Advertising
background image

Rockwell Automation Publication 1756-UM514C-EN-P - June 2014

161

PCCC Commands Supported by the Data Highway Plus Module

Appendix A

Reset DH+ Diagnostic Counters

After reading your 1756-DHRIO or 1756-DHRIOXT module’s diagnostic
counters, you can reset them back to zero to clear that block of your module’s
internal scratch RAM.

CMD = 06h, FNC = 07

28

Reply successfully received (high byte)

29

Command successfully received (low byte)

30

Command successfully received (high byte)

31

Reply successfully sent (low byte)

32

Reply successfully sent (high byte)

33

Reply could not be sent

34

Duplicate node detected

35

Duplicate token detected

36

Fatal out of memory

37

Underrun

38 - 127

Reserved / Read as 0

128

Number of Active Nodes

129 - 136

Active Node Table
A bit table where the LSB of offset 129 represents node 00 and the MSB of offset 136
represents node 77
If bit = 0, the node is not present
If bit = 1, the node is present

Byte

Description