Configuration information in dh+ messaging, Generate configuration faults – Rockwell Automation 1756-DHRIO_DHRIOXT ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual
Page 32
 
32
Rockwell Automation Publication 1756-UM514C-EN-P - June 2014
Chapter 2
Using the Data Highway Plus Network
Configuration Information in 
DH+ Messaging
When you are using DH+ messaging, you must use the default configuration or 
write configuration for your application.
The following configuration information is stored in the nonvolatile (NVS) 
memory on your 1756-DHRIO and 1756-DHRIOXT modules when you apply 
configuration by using the Studio 5000 environment:
•
Any routing table that can be needed to send DH+ messages through the 
module. - This information must be applied to the module’s configuration 
separately from other information. Use RSLinx to apply the routing table. 
For more information on routing tables, see page
•
Controller slot for each DH+ channel - This information must be applied 
to the module’s configuration separately from other information. For more 
information on setting the controller slot, see page 
.
•
Slot number of the module
•
Chassis serial number
Generate Configuration Faults
When you insert a 1756-DHRIO or 1756-DHRIOXT module in a 
ControlLogix chassis, the configuration information stored in the module’s NVS 
memory is compared to the slot and serial number of the chassis it is entering. If 
any information does not match, the 1756-DHRIO or1756-DHRIOXT 
module generates a configuration fault.
For a complete listing of the configuration faults that can be displayed on your 
1756-DHRIO and 1756-DHRIOXT modules, see 
IMPORTANT
If you restore defaults with Studio 5000 environment, the slot number and 
chassis serial number are stored in the 1756-DHRIO and 1756-DHRIOXT 
module’s nonvolatile memory, but no routing table is used and the 
controller slot for the DH+ channels is set to 0.