Troubleshooting the Module

What This Chapter Contains

This chapter describes your module’s diagnostics and methods of
troubleshooting your module.

Check Power Supply and
Module Status

On power-up, three events occur simultaneously:

Alphanumeric status indicator on the module illuminates and cycles
through the following sequence of messages:

Channel A and the network used for channel A - DH+ or RIO

Channel A node address, if used for DH+

Channel A status

Channel B and the network used for channel B - DH+ or RIO

Channel B node address, if used for DH+

Channel B status

This sequence runs continuously during normal module operation.

Module OK status indicator shows solid red and then flashes green

Power supply indicator shows solid green

Topic

Page

Check Power Supply and Module Status

153

Status Indicators

154

Minimizing False Received Frame with Bad CRC Messages

156

EXAMPLE

For example, if your module uses the following:

Channel A for DH+ with node address 14

Channel B for RIO

and the channels are operating properly, you see the following sequence:

A DH, A#14, A OK, B IO, SCAN, B OK