Using the 1756-DHRIO and 1756-DHRIOXT Modules in Remote I/O Applications
Chapter 9
Exchange I/O Data Between the Module and Adapters
I/O data is exchanged between the 1756-DHRIO or 1756-DHRIOXT module 
and adapters on the remote I/O link based on a list of adapters generated in the 
Studio 5000 environment.
The ControlLogix controller, as the 1756-DHRIO or1756-DHRIOXT 
module’s owner-controller, downloads this list, along with the remote I/O baud 
rate, to the 1756-DHRIO or1756-DHRIOXT module. The 1756-DHRIO or 
1756-DHRIOXT module scans each adapter (exchange I/O data) in the list in a 
round-robin fashion.
Exchange I/O Data Between the Module and the ControlLogix 
Controller
I/O data and status are exchanged between the 1756-DHRIO or 
1756-DHRIOXT module and the ControlLogix controller through the 
producer/consumer model used by the ControlLogix system.
Multiple connections are established between the 1756-DHRIO or 
1756-DHRIOXT module and the ControlLogix controller. These connections 
can be classified in two categories. In the first category, connections are 
established between the 1756-DHRIO or 1756-DHRIOXT module and the 
ControlLogix controller for each adapter on the remote I/O link. I/O data is 
exchanged on these connections.
In the second category, a connection is established between the supervisor of the 
remote I/O on the 1756-DHRIO or 1756-DHRIOXT module (the supervisor 
is the internal remote I/O scanner on the module) and the ControlLogix 
controller. Remote I/O scanner status is exchanged on this connection. In this 
case, the data exchange is bidirectional. The 1756-DHRIO or 1756-DHRIOXT 
module reports status on the remote I/O scanner, and the ControlLogix 
controller maintains ownership of the 1756-DHRIO or1756-DHRIOXT 
module.
I/O Configuration Tree in Studio 5000 Environment Controller 
Organizer
The I/O configuration tree in the Studio 5000 environment Controller 
Organizer specifies the connections to the 1756-DHRIO or 1756-DHRIOXT 
module and generates the adapter list of the 1756-DHRIO or 1756-DHRIOXT 
modules to scan.
IMPORTANT
Only one ControlLogix controller can communicate with and own the 
remote I/O channels on a 1756-DHRIO or 1756-DHRIOXT module.