Rockwell Automation Publication 1756-UM514C-EN-P - June 2014

17

About the Module

Chapter 1

Configure Switches

Before installing the module, you must set the network type switches for DH+ or
RIO, depending on your application. For a channel configured as DH+, you
must also select a node address within the range of 00-77. Node addresses are set
and displayed in octal.

Set the network type and node address switches as shown in the Figure.

IMPORTANT

If your module uses the 230k DH+ network (that is Channel A switch set to
3), Channel B is disabled.

Also, node address switches do not apply if you are using remote I/O.

Network type
switches (behind
cover)

20810

Node type
switches (behind
cover)

This example shows channel A
set for DH+ and channel B set
RIO

This example shows the channel A node
address at 010 and channel B at 024

Specify Network Type

Set Switch

Channel

A

DH+ - 57.6K

0

RIO Scanner

1

DH+ - 115K

2

DH+ - 230K

(Only channel A supports 230K

DH+. Channel B is disabled in this

mode.)

3

Not used

4-7

Channel

B

DH+ - 57.6K

0

RIO Scanner

1

DH+ - 115K

2

Not used

3-7

These node switches are not used with RIO.