Rockwell Automation 1756-DHRIO_DHRIOXT ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual

Page 155

Advertising
background image

Rockwell Automation Publication 1756-UM514C-EN-P - June 2014

155

Troubleshooting the Module

Chapter 13

Alphanumeric Indicator Status Message - Remote I/O

If the OK indicator is:

Module status is:

Take this action:

MUTE
LINK

No adapters found on remote I/O.

Add an adapter to the remote I/O
network.

RACK
OVER

Rack overlap on remote I/O.

Reconfigure remote I/O racks.

DUPL
SCAN

Duplicate scanner on remote I/O.

Check remote I/O adapter settings.

MAX_
DEV_

Maximum devices exceeded on remote
I/O.

Remove devices to meet limitations on
remote I/O network.

CHAT
LINK

Babble detected on remote I/O.

Check remote I/O device and network
connections.

OFF_
LINE

Not trying to communicate.

None. Normal state if controller is not
controlling remote I/O.

OK

Normal operation for that channel.

None.

Module Status - OK Indicator

If the OK indicator is:

Module status is:

Take this action:

Off

Not operating.

Apply chassis power. Verify module is
completely inserted into chassis and
backplane.

Green flashing

Operating, but not routing messages
and no controller transferring I/O.

None, if no messages are actively being
routed through the module and no
controller transferring I/O.
To route messages or transfer I/O, use
module default configuration or
configure module.

Red, then Off

Performing self-test.

None, normal operation.

Green

Operating and routing messages.

Verify module configuration.

Red

In major fault.

Restart module. If red reoccurs, replace
module.

Red flashing

In major fault or configuration fault.

Check alphanumeric indicator and take
action described in Alphanumeric
Indicator Status Message table.