Chapter 13

Troubleshooting the Module

Minimizing False Received
Frame with Bad CRC
Messages

1756-DHRIO and 1756-DHRIOXT modules that communicate with a
1784-KT or 1784-PCMK communication card on their DH+ link can receive
the following error message:

Received Frame with Bad CRC

This error does not affect DH+ link operations. To minimize its occurrence,
make sure that the DH+ link is terminated properly.

Channel Status - Channel A and Channel B Indicators

If the Channel A
or B
indicator is:

In this channel
mode:

Channel status is:

Take this action:

Off

All

Not online.

Place channel online.

Green

RIO scanner

Active RIO link. All adapter
modules are present and not
faulted.

None, normal operation

DH+

Operating.

None, normal operation.

Green flashing

RIO scanner

One or more nodes faulted or
failed.

Check power at other racks.

DH+

No other node on the network.

Check cables.

Red

All

Hardware fault.

Restart module. If red still on, replace
module.

Red flashing

RIO scanner

Faulted adapters detected.

Check cables. Check power at other
racks.

DH+

Duplicate node detected.

Check node address.