Rockwell Automation 1756-DHRIO_DHRIOXT ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual
Page 156
 
156
Rockwell Automation Publication 1756-UM514C-EN-P - June 2014
Chapter 13
Troubleshooting the Module
Minimizing False Received 
Frame with Bad CRC 
Messages
1756-DHRIO and 1756-DHRIOXT modules that communicate with a 
1784-KT or 1784-PCMK communication card on their DH+ link can receive 
the following error message:
Received Frame with Bad CRC
This error does not affect DH+ link operations. To minimize its occurrence, 
make sure that the DH+ link is terminated properly.
Channel Status - Channel A and Channel B Indicators
If the Channel A 
or B 
indicator is:
In this channel 
mode:
Channel status is:
Take this action:
Off
All
Not online.
Place channel online.
Green
RIO scanner
Active RIO link. All adapter 
modules are present and not 
faulted.
None, normal operation
DH+
Operating.
None, normal operation.
Green flashing
RIO scanner
One or more nodes faulted or 
failed.
Check power at other racks.
DH+
No other node on the network.
Check cables.
Red
All
Hardware fault.
Restart module. If red still on, replace 
module.
Red flashing
RIO scanner
Faulted adapters detected.
Check cables. Check power at other 
racks.
DH+
Duplicate node detected.
Check node address.