Using the Data Highway Plus Network

Chapter 2

Sending Local DH+ Messages on DH+

If a 1756-DHRIO channel receives a DH+ message with a destination link ID=0
from a ControlLogix controller in the same chassis, the module sends the
message as a local DH+ message.

Limitations of Local DH+ Messaging

When using Local DH+ Messaging, you must remember:

The DH+ message contains only a node ID for a node on the DH+
network.

A local DH+ message sent to the node ID of a port on the 1756-DHRIO
and 1756-DHRIOXT modules is forwarded to one user-configured
controller slot.

Messages on one DH+ network cannot be routed to other networks.

Routing Error in Local DH+ Messaging

If the module has a problem with routing a DH+ message, it can return a
response with an error status of D0 hex. A PLC-5 displays this error as D000 hex
when monitoring the message instruction. If you receive this error message,
perform the following actions:

Check your message instruction to make sure a destination node was
entered.

Check your default slot configuration to make sure that it matches the
location of the ControlLogix controller in the chassis.

Make sure power is applied to the module.

Programming Message Block Instructions in a Controller for Local DH+ Messaging

Before programming your message block instructions in your controller, you
must:

Determine which links send and receive DH+ Local messages.

Draw a network to make sure you meet the design requirements for Local
DH+ messages.

IMPORTANT

The target of the DH+ message must be on the same DH+ link as the 1756-
DHRIO and 1756-DHRIOXT modules sending the message. Also, the
ControlLogix controller must reside in the same chassis as the 1756-DHRIO
and 1756-DHRIOXT modules sending the message on DH+.