Configure the module switches, Configure a routing table for the module – Rockwell Automation 1756-DHRIO_DHRIOXT ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual

Page 86

Advertising
background image

86

Rockwell Automation Publication 1756-UM514C-EN-P - June 2014

Chapter 6

Messaging Between PLC-5 or SLC 5/04 Controllers and ControlLogix Controllers

Configure the Module Switches

In this application, you must set switches on the 1756-DHRIO and
1756-DHRIOXT modules for DH+ and the switches on the 1756-CNB
modules to the correct node addresses. The 1756-CNB module in system
number 1 uses node address 22 and the 1756-CNB module in system number 2
uses node address 23.

Configure a Routing Table for the Module

Use RSLinx software to configure a routing table for the 1756-DHRIO and
1756-DHRIOXT modules. The following figure shows the routing table
necessary for this example.

IMPORTANT

The switches on the 1756-CNB modules must match the information in the
1756-DHRIO routing table.