Rockwell Automation Publication 1756-UM514C-EN-P - June 2014

Chapter 12

Block Transfers with the 1756-DHRIO or 1756-DHRIOXT Module

Block Transfers to Remote
1771-ASB I/O Modules
through a
1756-DHRIO or 1756-
DHRIOXT Module in a Remote
Chassis

This application enables a ControlLogix controller to write block transfers to
remote 1771-ASB I/O modules through a 1756-DHRIO or 1756-DHRIOXT
module in a remote chassis over a ControlNet link. The following diagram
illustrates the steps you follow to use this application.

Configure the Module Switches

In this application, channel B on the 1756-DHRIO or 1756-DHRIOXT
module must be set for RIO. Channel A can be used for remote I/O or DH+,
regardless of the usage assigned to channel B.

Set the switches on the 1756-CNB modules to the correct network addresses.
The 1756-CNB module in system number 1 uses network address 01 and the
1756-CNB module in system number 2 uses network address 23.

1756-CNB
Network Address: 01

ControlLogix Controller

1756-CNB
Network Address: 23

1756-DHRIO

1771-ASB
Rack Number: 025