Configure the 1756-dhrio or 1756-dhrioxt – Rockwell Automation 1756-DHRIO_DHRIOXT ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual

Page 141

Advertising
background image

Rockwell Automation Publication 1756-UM514C-EN-P - June 2014

141

Connecting a ControlLogix Controller to Remote I/O

Chapter 11

Scan 1771 Remote I/O
Adapters through a
1756-DHRIO or
1756-DHRIOXT Module in a
Remote Chassis

In this application, a ControlLogix controller scans remote FLEX I/O modules
through a 1756-DHRIO or 1756-DHRIOXT module in a remote chassis over a
ControlNet network. The following figure illustrates the steps you follow to use
this application.

Configure the 1756-DHRIO or 1756-DHRIOXT Module Switches

In this application, channel B on the 1756-DHRIO or 1756-DHRIOXT
module must be set for RIO. Channel A can be used for remote I/O or DH+,
regardless of the usage assigned to channel B.

Configure the switches on the 1756-CNB modules to the correct node addresses.
The 1756-CNB module in system number 1 uses node address 01 and the
1756-CNB module in system number 2 uses node address 23.

1756-CNB
Network Address: 01

ControlLogix Controller

1771 I/O
Rack Number: 025
Starting Group 0
1/4 Rack

41421

ControlLogix Chassis 1

ControlLogix Chassis 2

1756-CNB
Network Address: 23

1756-DHRIO