Chapter 2
Using the Data Highway Plus Network
controller slot for port A is configured to “0”, the message is forwarded to the 
ControlLogix controller in slot 0.
Receiving Local DH+ Messages on DH+
Because a local DH+ message has only enough address information to get the 
message to a target node on the same DH+ network, the 1756-DHRIO and 
1756-DHRIOXT modules that receive this message cannot identify where to 
send the message. The 1756-DHRIO and 1756-DHRIOXT modules use the 
Controller Slot configuration parameter to send the message to the local 
controller.
You must use RSLinx software to configure the controller slot. For more 
information on setting the controller slot, see page 
.
Some messages, called PCCC commands, are not sent to the controller slot. In 
this case, the 1756-DHRIO and 1756-DHRIOXT modules generate a response 
to the message. For a complete list of these messages, see 
Local DH+ messaging does not require a populated routing table. Local DH+ 
messaging does require a default (that is a properly emptied) or an applied (that is 
a properly populated and saved) routing table, and a default or applied controller 
slot for each channel configured for DH+. For more information on routing 
tables, see 
,
1756- DHRIO
PLC-5 Controller B
Node Number: 025
Channel A
Node Number: 010
Controller Slot=0
ControlLogix Controller
41458
IMPORTANT
Local DH+ Messaging can target only one ControlLogix controller per DH+ 
channel. The ControlLogix controller must reside in the same chassis as the 
1756-DHRIO and 1756-DHRIOXT modules receiving the message.