Rpi formula without block transfer modules, Digital modules, Worst case scenario – Rockwell Automation 1756-DHRIO_DHRIOXT ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual

Page 166: Increase the unconnected message buffer limit, Digital modules worst case scenario

Advertising
background image

166

Rockwell Automation Publication 1756-UM514C-EN-P - June 2014

Appendix B

Application Guidelines and Tips

RPI Formula without Block
Transfer Modules

Digital Modules

This formula is for a worst case scenario with only discrete modules.

Scan Rate =

3ms/adapter for 230.4K Baud

5ms/adapter for 115.2K Baud

8ms/adapter for 57.6K Baud

Link Time = scan rate * (# of adapters)

Recommended RPI = 0.5 * link time

Maximum Update Time = RPI + 2 * (link time)

Worst Case Scenario

This formula is for a worst case scenario.

Scan Rate =

3ms/adapter for 230.4K Baud

5ms/adapter for 115.2K Baud

8ms/adapter for 57.6K Baud

Link time = scan rate * (# of adapters + # of adapters with block transfer
modules)

Recommended RPI = 0.5 * link time

Maximum Update Time = RPI + 2 * (link time)

Increase the Unconnected
Message Buffer Limit

You can find more information on increasing the unconnected message buffer
limit at the Rockwell Automation knowledge base at:

https://rockwellautomation.custhelp.com/

With RSLogix 5000 version 8.02 the Unconnected Message Buffer can be
increased from the default value of 10 to a total of 40 with a CIP Generic
Message instruction.

A penalty of 1K of I/O memory is consumed for each increase above 10

A source and destination array must be configured. Each needs to be
configured as SINT type with 30 arrays.

The communication path is set to: 1, slot number of the controller.

The CIP Generic message has to be enabled once, after that another CIP
Generic message must be used to change the value.

Advertising