Configure message instructions – Rockwell Automation 1756-DHRIO_DHRIOXT ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual

Page 82

Advertising
background image

82

Rockwell Automation Publication 1756-UM514C-EN-P - June 2014

Chapter 6

Messaging Between PLC-5 or SLC 5/04 Controllers and ControlLogix Controllers

Configure Message Instructions

You must use RSLogix 5 software to configure the PLC-5 message instructions.
The following figure shows a message instruction necessary for this example.

IMPORTANT

If the ControlLogix controller in this example is the destination of a
PCCC-typed message, you must remember the following:

When a PLC5, SLC500, PLC5/250, PLC3, or PLC2 sends a message to a

controller on ControlLogix, a mapping table is needed to be configured
in the Studio 5000 environment.

In the Logic tab on the tool bar select Map PLC or SLC Messages

The file number must be an integer type. Just write the file number in

the box. The whole file in the PLC or SLC controller will be used starting
with word 0.

A tag must be created beforehand to accept the data with the proper

number of array elements.

The destination tag in the PLC or SLC message is the file number

configured at the word level.

Advertising