Chapter 13

Troubleshooting the Module

Status Indicators

The following figure and tables describe the module status indicators.

If after powerup, the alphanumeric indicator does not start cycling (or if it stops
cycling) through these messages, see the following tables.

Data Highway Plus

Sequence of display

Where

A DH
A#xx
xxxx

A is the channel (A or B) and DH indicates network type is DH+.
xx is the channel’s node address.
xxxx is the channel’s status message.

Remote I/O

Sequence of display

Where

BIO
SCAN
xxxx

B is the channel (A or B) and IO indicates network type is Remote I/O.
SCAN indicates scanner.
xxxx is the channel’s status message.

Power Supply Indicator

If the power indicator is:

Power supply is:

Take this action:

Off

Not operating

Turn power switch ON.
Check power wiring connections.
Check fuse.

On

Operating

None; normal operation

Alphanumeric Indicator Status Message - Data Highway Plus

If the alphanumeric
indicator status message
shows:

Network status is:

Take this action:

OFF
LINE

Data Highway Plus link is in STOP state.

Correct the configuration.

DUPL
NODE

Data Highway Plus Duplicate node
address.

Select another node address and reset
switches.

ONLY
NODE

Only node on Data Highway Plus link.

Check cables.

CNFG
FALT

Incorrect Data Highway Plus routing
table configuration.
Incorrect Data Highway object
configuration.

Verify the module is inserted into the
correct slot.

OK

Normal operation for that channel.

None.

CHA CHB

OK

H+/RIO

43241

Power Supply Indicator is
green.

Alphanumeric Status Indicator illuminates and cycles through a
sequence of messages.

Module OK status indicator is solid red,
then flashing green.