What this chapter contains, Block transfer fault notification, Chapter 12 – Rockwell Automation 1756-DHRIO_DHRIOXT ControlLogix Data Highway Plus-Remote I/O Communication Interface Module User Manual
Page 145: Chapter
 
Rockwell Automation Publication 1756-UM514C-EN-P - June 2014
145
Chapter
12
Block Transfers with the 1756-DHRIO or 
1756-DHRIOXT Module
What This Chapter Contains
This chapter describes how to use the 1756-DHRIO or 1756-DHRIOXT 
module to connect a ControlLogix controller to a remote I/O Block Transfer 
(BT) module.
The 1756-DHRIO and 1756-DHRIOXT modules support sending block 
transfer (BT) data and discrete I/O to the ControlLogix controller. This data 
exchange transfers up to 64 words of data to/from a selected I/O module.
The BT data exchange is message-based (that is a message instruction in the 
Ladder Logic program of the ControlLogix controller must be used to initiate 
the BT request). In the case of digital I/O modules, simply by entering the 
adapter in the ControlLogix controller organizer, data is transferred without 
requiring instructions.
The process for completing block transfers on remote I/O remains consistent 
with all adapters products. The remote I/O network characteristics defined for 
the PLC-5 remote I/O scanner are the same for the 1756-DHRIO remote I/O 
scanner.
Block Transfer Fault 
Notification
The message timeout for the BT message is fixed at 4.5 seconds. This timeout is a 
ControlLogix network response timeout associated with the connection 
established between the 1756-DHRIO or 1756-DHRIOXT module and the 
ControlLogix controller. The primary timeout for the BT response is remote I/O 
network based. This timeout occurs in 4 seconds if the I/O module fails to 
respond to the BT message.