The ready-made cables from Pilz are low capacity. The leakage current

can be calculated approximately as follows (at 400 V mains voltage):

I

abl

= n x 20 mA + L x 1 mA/m at 8 kHz clock frequency at the output

stage

I

abl

= n x 20 mA + L x 2 mA/m at 16 kHz clock frequency at the output

stage

I

abl

= leakage current, n = number of servo amplifiers, L = length of mo-

tor cable

With other mains voltages, the leakage current will vary in proportion to

the voltage.

Example: 2 x servo amplifiers + 25 m motor cable at 8 kHz clock fre-

quency:

2 x 20 mA + 25 m x 1 mA/m = 65 mA leakage current.

The following measures can be taken to minimise leakage currents:

Reduce the length of the motor cable

Use lower capacity cables (see section entitled “Connection cables”)

Remove external EMC filters (interference suppression measures are

integrated within the servo amplifier)

6.3.1.2

Residual current devices FI

Residual current devices FI

6-

][Verdr_FI

In accordance with DIN IEC 60364-4-41 - Electrical Installations of

Buildings - and EN 60204 - Electrical Equipment of Machines - it is pos-

sible to use residual current devices (hereafter called FI), if the necessary

provisions are met.

The servo amplifiers constitute a 3-phase system with a B6 bridge. Uni-

versal current sensitive FIs must be used to enable any potential DC fault

current to be detected.

INFORMATION

The leakage current to PE is more than 3.5 mA. In accordance

with EN 61800-5-1, the PE connection must either be duplicated

or a connection cable with a cross section > 10 mm² must be

used. Use the PE terminal and PE bolt.