Ambient conditions

Ambient conditions

3-

][Sicherheit_Bestimmung_Umgebung

Please note the following conditions for using the servo amplifier:

Operation of the servo amplifier is forbidden in the following condi-

tions:

– Potentially explosive areas

– Environments containing corrosive and/or conductive acids, alka-

line solutions, oils, fumes or dusts

– Where there is a direct connection to unearthed or asymmetrically

earthed mains supplies with U

N

> 240 V. See chapter entitled “Wir-

ing”, section on “Mains voltage”.

– On ships and offshore installations

The servo amplifier may only be operated in an enclosed control cab-

inet in compliance with the ambient conditions defined under “Tech-

nical details”. Ventilation or cooling may be required to maintain the

control cabinet temperature below 40 °C.

][EMV_Wohnumgebung

3.1.4

Guidelines for UL approval

Guidelines for UL approval

3-

][Sicherheit_Bestimmung_UL_D_48_72

Please note the following guidelines for UL approval:

Only use copper wiring that can withstand temperatures of 60°/75°C.

Clamping torque for power connection terminals:

X0: 8-2 AWG, TQ Lb In. 40

X8: 8-2 AWG, TQ Lb In. 40

Only use the servo amplifier in max. pollution degree 2 environments.

The servo amplifier can be used on supply networks that are able to

provide no more than 42 kA symmetrical at a maximum voltage of 480

VAC.

WARNING!

In a residential environment this product may cause high-fre-

quency noise, so that suppression measures may be required.