Comissioning and Configuration

4.7

Restoring the delivery state

Restoring the delivery state To restore the delivery state for backup objects in ELxxxx terminals, the CoE
object Restore default parameters, SubIndex 001 can be selected in the TwinCAT System Manager (Config
mode).

Fig. 65: Selecting the Restore default parameters PDO

Double-click on SubIndex 001 to enter the Set Value dialog. Enter the value 1684107116 in field Dec or the
value 0x64616F6C in field Hex and confirm with OK.

All backup objects are reset to the delivery state.

Fig. 66: Entering a restore value in the Set Value dialog

Note

Alternative restore value

In some older terminals the backup objects can be switched with an alternative restore
value:
Decimal value: 1819238756
Hexadecimal value: 0x6C6F6164

An incorrect entry for the restore value has no effect.