1 index 6000 dpo inputs ch.1, 2 index 6010 dpo inputs ch.2 – BECKHOFF EP9214-0023 User Manual

Page 56

Advertising
background image

Comissioning and Configuration

4.5.1.3.1

Index 6000 DPO Inputs Ch.1

Index

Name

Meaning

Data type

Flags

Default

6000:0

DPO Inputs
Ch.1

Input of the first channel

UINT8

RO

0x10 (16

dec

)

6000:01

Error Us

The current monitoring of Us has tripped. The bit must be
reset by a ‘Global Reset’ (F707:04) or by the corresponding
Reset Us (7000:05). The output cannot be activated as
long as the bit is 1.

boolean

RO

0x00 (0

dec

)

6000:02

Error Up

The current monitoring of Up has tripped.

boolean

RO

0x00 (0

dec

)

6000:03

Warning Us

The monitoring has detected overcurrent; the switching off
of output Us on this channel is imminent if the current con-
sumption of the branch does not decrease.

boolean

RO

0x00 (0

dec

)

6000:04

Warning Up

The monitoring has detected overcurrent; the switching off
of output Us on this channel is imminent if the current con-
sumption of the branch does not decrease.

boolean

RO

0x00 (0

dec

)

6000:05

Status Us

0: The output is switched off
1: The output supplies 24 V

boolean

RO

0x00 (0

dec

)

6000:06

Status Up

0: The output is switched off
1: The output supplies 24 V

boolean

RO

0x00 (0

dec

)

6000:07

Channel Error

6000:01 or 6000:02 are set

boolean

RO

0x00 (0

dec

)

6000:0E

Sync error

boolean

RO

0x00 (0

dec

)

6000:0F

TxPDO State

boolean

RO

0x00 (0

dec

)

6000:10

TxPDO Toggle

boolean

RO

0x00 (0

dec

)

4.5.1.3.2

Index 6010 DPO Inputs Ch.2

Index

Name

Meaning

Data type

Flags

Default

6010:0

DPO Inputs
Ch.2

Input of the first channel

UINT8

RO

0x10 (16

dec

)

6010:01

Error Us

The current monitoring of Us has tripped. The bit must be
reset by a ‘Global Reset’ (F707:04) or by the corresponding
Reset Us (7000:05). The output cannot be activated as
long as the bit is 1.

boolean

RO

0x00 (0

dec

)

6010:02

Error Up

The current monitoring of Up has tripped.

boolean

RO

0x00 (0

dec

)

6010:03

Warning Us

The monitoring has detected overcurrent; the switching off
of output Us on this channel is imminent if the current con-
sumption of the branch does not decrease.

boolean

RO

0x00 (0

dec

)

6010:04

Warning Up

The monitoring has detected overcurrent; the switching off
of output Us on this channel is imminent if the current con-
sumption of the branch does not decrease.

boolean

RO

0x00 (0

dec

)

6010:05

Status Us

0: The output is switched off
1: The output supplies 24 V

boolean

RO

0x00 (0

dec

)

6010:06

Status Up

0: The output is switched off
1: The output supplies 24 V

boolean

RO

0x00 (0

dec

)

6010:07

Channel Error

6010:01 or 6010:02 are set

boolean

RO

0x00 (0

dec

)

6010:0E

Sync error

boolean

RO

0x00 (0

dec

)

6010:0F

TxPDO State

boolean

RO

0x00 (0

dec

)

6010:10

TxPDO Toggle

boolean

RO

0x00 (0

dec

)

EP9214-0023 and EP9224-0023