Comissioning and Configuration

4.5

EP9214-0023

4.5.1

EP9214-0023 - Object description

Note

Parameterization

Terminals' parameterization will be conducted by the CoE tab (double-click on the referring
object) or the Process data tab (PDO assignment)

Note

EtherCAT XML Device Description

The description correspond to the display of the CoE objects from the EtherCAT XML De-
vice Description. It is strongly recommended to download the latest revision of the corre-
sponding XML file from the Beckhoff website (http://www.beckhoff.com/english/default.htm?
download/elconfg.htm) and follow the installation instructions.

The CoE overview contains objects for different intended applications:

• Objects required for parameterization during commissioning

• Objects intended for regular operation e.g. through ADS access

• Objects for indicating internal settings (may be fixed)

• Further profile-specific objects indicating inputs, outputs and status information

The following section first describes the objects require for normal operation, followed by a complete
overview of missing objects.

4.5.1.1

Objects for parameterization

4.5.1.1.1

Index 1011 Restore default parameters

Index

Name

Meaning

Data
type

Flags

Default

1011:0

Restore
default
parameters

Making default settings

UINT8

RO

0x01 (1

dec

)

1011:01 SubIndex

001

If this object is set to "0x64616F6C" in the set
value dialog, all backup objects are reset to
their delivery state.

UINT32

RW

0x00000000
(0

dec

)

Index

Name

Meaning

Data type

Flags

Default

8000:0

DPO Settings
Ch.1

UINT8

RO

0x13 (19

dec

)

8000:02

Default State Us The output adopts this value if F707:01 is not set

boolean

RW

0x01 (1

dec

)

8000:03

Default State Up The output adopts this value if F707:01 is not set

boolean

RW

0x01 (1

dec

)

8000:11

Characteristic

Specifies the characteristic with which the current monitor-
ing reacts:
0

dec

: very fast acting

1

dec

: fast acting

2

dec

: slow acting

3

dec

: time delay

UINT16

RW

0x0001 (1

dec

)

8000:12

Nominal Current
Us

Nominal maximum current at the output

UINT16

RW

0x0FA0 (4000

dec

)

8000:13

Nominal Current
Up

Nominal maximum current at the output

UINT16

RW

0x0FA0 (4000

dec

)

EP9214-0023 and EP9224-0023

45

Version 2.0.0

Advertising