4 technical data – BECKHOFF EP9214-0023 User Manual

Page 11

Advertising
background image

Product overview

Quick links

Installation

Configuration

UL requirements for UL approved modules

2.4

Technical data

Technical data

EP9214-0023

EP9224-0023

Rated voltage

24 V

DC

(-15 % / +20 %)

Power supply

Feed: Plug 7/8", max. 16 A for each Us/Up
Onward connection: Socket 7/8", max. 16 A for each Us/Up

Number of load outputs

4 x M8, for each Us and Up

Voltage drop V

ON

in the load

circuits

90 mV / Ampere

Parallel connection of several load
outputs

not permissible

Overload switch-off

dependent on selected load curve (20 ms at 3 x I

N

, see time/current

characteristics)

Temperature switch-off

Internal temperature switch-off

Switch-on delay

10, 100 or 200 ms (adjustable via CoE)

Selectivity

in case of an error, the channel concerned is switched off

Signalling contact

1

Reset contact

1

Connections for signal and reset
contacts

in : 1 x M8 plug
out : 1 x M8 socket

Fieldbus

EtherCAT

Fieldbus connection

2 x M8 sockets, screened, marked green

Electrical isolation

Control voltage/fieldbus: 500 V

Supply of the module circuitry

from the control voltage Us

Current consumption of the module
circuitry

typically 110 mA from Us,
typically 40 mA from Up

Process image

Inputs: 5 x 16 bit
Outputs: 5 x 16 bit

Inputs: 16 x 16 Bit
Outputs: 5 x 16 Bit

Data logging

-

40 samples ( 1 ms - 1000 ms
sample time)

Permissible ambient temperature
during operation

-25°C ... +60°C

Permissible ambient temperature
during storage

-25 °C... +85°C

Vibration / shock resistance

conforms to EN 60068-2-6 / EN 60068-2-27

EMC immunity/emission

conforms to EN 61000-6-2 / EN 61000-6-4

Dimensions

126 mm x 60 mm x 40  mm

Weight

approx. 450 g

Installation position

variable

Protection class

IP65, IP66, IP67 (according to EN 60529)

Approvals

CE, UL in preparation

EP9214-0023 and EP9224-0023