4.6.2.3.4

Index 6030 DPO Inputs Ch.4

Index

Name

Meaning

Data type

Flags

Default

6030:0

DPO Inputs Ch.4

Input of the first channel

UINT8

RO

0x18 (24

dec

)

6030:01

Error Us

The current monitoring of Us
has tripped. The bit must be re-
set by a Global Reset (F707:04)
or by the corresponding Reset
Us (7030:05). The output can-
not be activated as long as the
bit is set.

boolean

RO

0x00 (0

dec

)

6030:02

Error Up

The current monitoring of Up
has tripped. The bit must be re-
set by a Global Reset (F707:04)
or by the corresponding Reset
Us (7030:06). The output can-
not be activated as long as the
bit is set.

boolean

RO

0x00 (0

dec

)

6030:03

Warning Us

The monitoring has detected
overcurrent; the switching off of
output Us on this channel is im-
minent if the current consump-
tion of the branch does not de-
crease.

boolean

RO

0x00 (0

dec

)

6030:04

Warning Up

The monitoring has detected
overcurrent; the switching off of
output Us on this channel is im-
minent if the current consump-
tion of the branch does not de-
crease.

boolean

RO

0x00 (0

dec

)

6030:05

Status Us

0

bin

: The output is switched off

1

bin

: The output supplies 24 V

boolean

RO

0x00 (0

dec

)

6030:06

Status Up

0

bin

: The output is switched off

1

bin

: The output supplies 24 V

boolean

RO

0x00 (0

dec

)

6030:07

Channel Error

6030:01 or 6030:02 are set

boolean

RO

0x00 (0

dec

)

6030:08

Error Sum Current

Sum current oft he channel has
been exceeded. So the output
is switched off. An active reset
is required to set the output
again.

boolean

RO

0x00 (0

dec

)

6030:09

Warning Sum Current

An overcurrent peak has beenn
detected. If the output will be
loaded furtermore in this way it
will switch of.

boolean

RO

0x00 (0

dec

)

6030:0F

TxPDO State

boolean

RO

0x00 (0

dec

)

6030:10

TxPDO Toggle

boolean

RO

0x00 (0

dec

)

6030:11

Current Us

Current from Us

INT16

RO

0x0000 (0

dec

)

6030:12

Current Up

Current from Up

INT16

RO

0x0000 (0

dec

)

6030:13

Peak Value 1

Peak value of the 1. item, that
was measured for extended di-
agnosis of channel 4.

INT16

RO

0x0000 (0

dec

)

6030:14

Peak Value 2

Peak value of the 2. item, that
was measured for extended di-
agnosis of channel 4.

INT16

RO

0x0000 (0

dec

)

6030:17

Timestamp 1

Time stamp when the peak
value 6030:13 was measured

UINT64

RO

6030:18

Timestamp 2

Time stamp when the peak
value 6030:14 was measured

UINT64

RO

4.6.2.3.5

Index 6040 LOG Status

Index

Name

Meaning

Data type

Flags

Default

6040:0

LOG Status

UINT8

RO

0x12 (18

dec

)

6040:01

Logger Running

0: Logger still running

boolean

RO

0x00 (0

dec

)

6040:11

Elapsed Time

Time since the logger was
stopped

UINT32

RO

0x00000000 (0

dec

)

6040:12

Trigger Reason

Reason the logger was stopped
for

UINT16

RO

0x0000 (0

dec

)

EP9214-0023 and EP9224-0023