4 power cable conductor losses – BECKHOFF EP9214-0023 User Manual

Page 21

Advertising
background image

Mounting and cabling

3.3.4

Power cable conductor losses

The ZK2020-xxxx-yyyy power cables should not exceed the total length of 15 m at 4 A (with continuation).
When planning the cabling, note that at 24 V nominal voltage, the functionality of the module can no longer
be assured if the voltage drop reaches 6 V. Variations in the output voltage from the power supply unit must
also be taken into account.

Fig. 17: Power cable conductor losses

Example

8 m power cable with 0.34 mm² cross-section has a voltage drop of 3.2 V at 4 A.

Note

EP92x4 Power Distribution Modules

With EP9214 and EP9224 Power Distribution Modules intelligent concepts for voltage sup-
ply are available. Further information may be found under www.beckhoff.com/EP9224.

EP9214-0023 and EP9224-0023

21