Comissioning and Configuration

Fig. 64: EP9224 - logdata.csv

Description:

• EP9224: Setting the Us channel to a nominal current of 1500 mA

• Continuous increase of the current on channel 1 Us within the recorded range of 3.0 A to 4.9 A, then

shut-off takes place.

• Overcurrent begins from 180 ms

• 100% overload reached (99), channel is switched off

• the module now waits for an error correction or an active reset of the error

EP9214-0023 and EP9224-0023