Comissioning and Configuration

4.4.2

Current limitation, switching the load circuits off

The switch-off behavior of the individual load circuits can be adapted to the application.

The following modes can be set individually for each channel:

• Very fast acting

• Fast acting

• Slow acting

• Time delay

Release time (switch-off time) of the modes

Rated current

Very fast acting

Fast acting

Slow acting

Time delay

100 %

1 h

-

-

-

110 %

1 h

4 h

-

-

120 %

7 min

4  h

-

-

150 %

30 s

30 min

1 h

4 h

210 %

500 ms

20 sec

20 s

100 s

275 %

500 ms

1 sec

20 s

10 s

300 %

20 ms

100 ms

1 s

3 s

The release time depends on the set rated current.

Following the switch-off of a channel it is necessary to reactivate it after rectification of the cause of the error.

Switch-off of the box due to overtemperature

The EP9214 is internally protected against overheating. A warning is given in the process data if a
temperature of about 75°C is reached.

Fig. 42: Temperature Warning and Temperature Error bits

On reaching 85°C all load circuits are switched off in order to protect the hardware against destruction. In
this case the Temperature Error bit is set.

So that the permitted temperature is not exceeded, the box is to be mounted with its rear wall on the flattest
possible thermally conductive surface.

EP9214-0023 and EP9224-0023

41