5 monitoring and reset contacts – BECKHOFF EP9214-0023 User Manual

Page 26

Advertising
background image

Mounting and cabling

Initialization

When switching on the voltage supply to the EP9214 / EP9224, all green LEDs and then all red LEDs are
switched on briefly to test the LEDs.

The LED is valid for both voltages and currents (Us and Up; OR).

LED

Status
Us / Up

Warning

Error
Us / Up

Description

Off

0

0

0

The output is ready

Green

1

0

0

The output is just switching on

Green

1

0

0

The output is switched on. Normal operating status.

Flashing
green

1

1

0

The output is still operating, but will switch off if conditions
remain unchanged (Warning Ux).

Flashing
red

0

1

1

The output has been switched off. Switching on again is not
yet possible (waiting time of 20 seconds)

Red

0

0

1

The output has been deactivated and can be returned to a
normal state by a reset.

3.5

Monitoring and reset contacts

The EP9214 has a monitoring contact (signal contact) and a reset contact. These contacts are fed out via an
M8 plug and an M8 socket.

The contacts of this M8 plug and M8 socket are wired together 1:1.

Fig. 24: EP9214 - Monitoring and reset connectors

Pin assignment

Fig. 25: EP9214 - Monitoring and reset contacts

EP9214-0023 and EP9224-0023

26