4 comissioning and configuration, 1 inserting into the ethercat network, 4comissioning and configuration – BECKHOFF EP9214-0023 User Manual

Page 28

Advertising
background image

Comissioning and Configuration

4

Comissioning and Configuration

4.1

Inserting into the EtherCAT network

Note

Installation of the latest XML device description

Please ensure that you have installed the latest XML device description in TwinCAT. This
can be downloaded from the Beckhoff website (http://www.beckhoff.de/english/default.htm?
download/elconfg.htm) and installed according to the installation instructions.

At the Beckhoff TwinCAT System Manager the configuration tree can be build in two different ways:

by scanning [

}

 28] for existing hardware (called "online") and

by manual inserting/appending [

}

 28] of fieldbus devices, couplers and slaves.

Automatic scanning in of the box

• The EtherCAT system must be in a safe, de-energized state before the EtherCAT modules are

connected to the EtherCAT network!

Switch on the operating voltage, open the TwinCAT System Manager [

}

 31] (Config mode), and scan

in the devices (see Fig. 1). Acknowledge all dialogs with "OK", so that the configuration is in "FreeRun"
mode.

Fig. 26: Scanning in the configuration (I/O Devices -> right-click -> Scan Devices...)

Appending a module manually

• The EtherCAT system must be in a safe, de-energized state before the EtherCAT modules are

connected to the EtherCAT network!

Switch on the operating voltage, open the TwinCAT System Manager [

}

 31] (Config mode)

• Append a new I/O device. In the dialog that appears select the device EtherCAT (Direct Mode), and

confirm with OK.

EP9214-0023 and EP9224-0023

28

Version 2.0.0

Advertising
This manual is related to the following products: