Comissioning and Configuration

The release time depends on the set rated current.

CoE parameters for setting the current limiting characteristic

Fig. 44: CoE parameters for setting the current limiting characteristic

Meaning of the parameters

Index

Name

Meaning

0x80n0:02

Default State Us

TRUE: in case of operation without fieldbus the load circuit Us of
channel n is automatically switched on

FALSE: in case of operation without fieldbus the load circuit Us of
channel n remains switched off

0x80n0:02

Default State Up

TRUE: in case of operation without fieldbus the load circuit Up of
channel n is automatically switched on

FALSE: in case of operation without fieldbus the load circuit Up of
channel n remains switched off

0x80n0:11

Characteristic

Release time depending on rated current

0x80n0:12

Nominal Current Us Specification of the rated current of Us in mA

0x80n0:13

Nominal Current Up Specification of the rated current of Up in mA

Switching load circuits on again after switch-off

This takes place either via the process data [

}

 61] by EtherCAT or by the reset input [

}

 26] directly on the

box.

4.4.4

Status LEDs and status bits

Below is a table showing the meaning of the status LEDs and status bits for the power outputs (EP9214 for
example):

EP9214-0023 and EP9224-0023