Comissioning and Configuration

Reset of the values

Reset of Peak Value n and Timestamp for each channel

Fig. 57: EP9224 - Reset extended diag data for the channel

Reset of Peak Value n and Timestamp of the module

Fig. 58: EP9224 - Reset extended diag data for the module

4.6.1.5

Data logging

Overview

With the data logging the continuous logging of all relevant EP9224 data can be started.

These data are written to a 40-line ring buffer.

On the first error the recording is stopped so that the data can be evaluated after an error or during normal
operation.

In the event of an error, data are still written for a few cycles. The switching-off of a channel is indicated by
OFF.

The writing rate or scanning rate is 10 ms in the factory setting. The value can be adjusted from 1 ms to
1000 ms in the CoE.

EP9214-0023 and EP9224-0023

69

Version 2.0.0