Comissioning and Configuration

Fig. 45: EP9214 - Status bits

Fig. 46: EP9214 - status bits

Initialization

When switching on the voltage supply to the EP9214/EP9224, all green LEDs and then all red LEDs are
switched on briefly to test the LEDs.

The LED is valid for both voltages and currents (Us and Up; OR).

LED

Status
Us / Up

Warning

Error
Us / Up

Description

Off

0

0

0

The output is ready

Green

1

0

0

The output is just switching on

Green

1

0

0

The output is switched on. Normal operating
status.

Flashing green

1

1

0

The output is still operating, but will switch off if
conditions remain unchanged (Warning Ux).

Flashing red

0

1

1

The output has been switched off. Switching on
again is not yet possible (waiting time of
20 seconds)

Red

0

0

1

The output has been deactivated and can be
returned to a normal state by a reset.