Comissioning and Configuration

4.6.2.1.2

Index 8000 DPO Settings Ch.1

Index

Name

Meaning

Data type

Flags

Default

8000:0

DPO Set-
tings Ch.1

UINT8

RO

0x16 (22

dec

)

8000:02

Default
State Us

The output adopts this value if Enable Control via
Fieldbus
(F707:01) is not set or no connection to the
fieldbus

boolean

RW

0x01 (1

dec

)

8000:03

Default
State Up

The output adopts this value if Enable Control via
Fieldbus
(F707:01) is not set or no connection to the
fieldbus

boolean

RW

0x01 (1

dec

)

8000:04

Enable Sum
Current Lim-
itation

Sum current limitation:
0

bin

: disabled

1

bin

: enabled

boolean

RW

0x00 (0

dec

)

8000:11

Characteris-
tic

Specifies the characteristic with which the current
monitoring reacts:
0

dec

: very fast acting

1

dec

: fast acting

2

dec

: slow acting

3

dec

: time delay

UINT16

RW

0x0001 (1

dec

)

8000:12

Nominal
Current Us

Nominal current at the output

UINT16

RW

0x0FA0 (4000

dec

)

8000:13

Nominal
Current Up

Nominal current at the output

UINT16

RW

0x0FA0 (4000

dec

)

8000:14

Nominal
Sum Cur-
rent 

Nominal total current

UINT16

RW

0x0FA0 (4000

dec

)

8000:15

Timestamp
1 Trigger

Trigger condition for extended diagnosis

UINT16

RW

0x0000 (0

dec

)

8000:16

Timestamp
2 Trigger

Trigger condition for extended diagnosis

UINT16

RW

0x0000 (0

dec

)

4.6.2.1.3

Index 8010 DPO Settings Ch.2

Index

Name

Meaning

Data type

Flags

Default

8010:0

DPO Set-
tings Ch.2

UINT8

RO

0x16 (22

dec

)

8010:02

Default
State Us

The output adopts this value if Enable Control via
Fieldbus
(F707:01) is not set or no connection to the
fieldbus

boolean

RW

0x01 (1

dec

)

8010:03

Default
State Up

The output adopts this value if Enable Control via
Fieldbus
(F707:01) is not set or no connection to the
fieldbus

boolean

RW

0x01 (1

dec

)

8010:04

Enable Sum
Current Lim-
itation

Sum current limitation:
0

bin

: disabled

1

bin

: enabled

boolean

RW

0x00 (0

dec

)

8010:11

Characteris-
tic

Specifies the characteristic with which the current
monitoring reacts:
0

dec

: very fast acting

1

dec

: fast acting

2

dec

: slow acting

3

dec

: time delay

UINT16

RW

0x0001 (1

dec

)

8010:12

Nominal
Current Us

Nominal current at the output

UINT16

RW

0x0FA0 (4000

dec

)

8010:13

Nominal
Current Up

Nominal current at the output

UINT16

RW

0x0FA0 (4000

dec

)

8010:14

Nominal
Sum Cur-
rent 

Nominal total current

UINT16

RW

0x0FA0 (4000

dec

)

8010:15

Timestamp
1 Trigger

Trigger condition for extended diagnosis

UINT16

RW

0x0000 (0

dec

)

8010:16

Timestamp
2 Trigger

Trigger condition for extended diagnosis

UINT16

RW

0x0000 (0

dec

)

EP9214-0023 and EP9224-0023