7 index f607 dpo inputs device – BECKHOFF EP9214-0023 User Manual

Page 79

Advertising
background image

Comissioning and Configuration

4.6.2.1.7

Index F607 DPO Inputs Device

Index

Name

Meaning

Data type

Flags

Default

F607:0

DPO Inputs Device

UINT8

RO

0x19 (25

dec

)

F607:01

Temperature Warning

A temperature of about 80°C
has been reached

boolean

RO

0x00 (0

dec

)

F607:02

Temperature Error

A critical temperature of about
85°C has been reached, the
outputs will be switched off. The
bit must be reset by a Global
Reset
(F707:04) or by a voltage
reset. No output can be
switched on if the error bit is
set.

boolean

RO

0x00 (0

dec

)

F607:03

Us Warning

Us is less than 21.5 V, no fur-
ther outputs can be switched
on.

boolean

RO

0x00 (0

dec

)

F607:04

Us Error

Us is less than 19 V, all Us out-
puts will be switched off. The bit
must be reset by a Global Re-
set
(F707:04) or by a voltage
reset. No Us output can be
switched on if the error bit is
set.

boolean

RO

0x00 (0

dec

)

F607:05

Up Warning

Up is less than 21.5 V, no fur-
ther outputs can be switched
on.

boolean

RO

0x00 (0

dec

)

F607:06

Up Error

Up is less than 19 V, all Up out-
puts will be switched off. The bit
must be reset by a Global Re-
set
(F707:04) or by a voltage
reset. No Up output can be
switched on if the error bit is
set.

boolean

RO

0x00 (0

dec

)

F607:07

Global Error Bit

One of the error bits of the four
channels or F607:02 or F607:04
or F607:06 is set

boolean

RO

0x00 (0

dec

)

F607:08

Sum Current Warning

Sum current monitoring has de-
sected a peak current

boolean

RO

0x00 (0

dec

)

F607:09

Sum Current Error

Sum current monitoring has de-
sected an over current. All out-
puts are switched off

boolean

RO

0x00 (0

dec

)

F607:0C

Reset Input

Us is less than 21.5 V, no fur-
ther outputs can be switched
on.

boolean

RO

0x00 (0

dec

)

F607:0F

TxPDO State

boolean

RO

0x00 (0

dec

)

F607:10

TxPDO Toggle

boolean

RO

0x00 (0

dec

)

F607:11

Current Us

Sum current of the module at
Us

INT16

RO

0x0000 (0

dec

)

F607:12

Current Up

Sum current of the module at
Up

INT16

RO

0x0000 (0

dec

)

F607:13

Voltage Us

Voltage at input Us

INT16

RO

0x0000 (0

dec

)

F607:14

Voltage Up

Voltage at input Up

INT16

RO

0x0000 (0

dec

)

F607:15

Temperature

Internal temperature of power
stage

INT16

RO

0x0000 (0

dec

)

F607:16

Peak Value 1

Extended diagnosis

INT16

RO

0x0000 (0

dec

)

F607:17

Peak Value 2

Extended diagnosis

INT16

RO

0x0000 (0

dec

)

F607:18

Timestamp 1

UINT64

RO

F607:19

Timestamp 2

UINT64

RO