33 index 1c33 sm input parameter, 3 profile-specific objects (0x6000-0xffff) – BECKHOFF EP9214-0023 User Manual

Page 94

Advertising
background image

Comissioning and Configuration

4.6.2.2.33

Index 1C33 SM input parameter

Index

Name

Meaning

Data type

Flags

Default

1C33:0

SM input
parameter

Synchronization parameters for the inputs

UINT8

RO

0x20 (32

dec

)

1C33:01

Sync mode

Current synchronization mode:

• 0: Free Run

• 1: Synchronous with SM 3 event (no outputs

available)

• 2: DC - Synchronous with SYNC0 Event

• 3: DC - Synchronous with SYNC1 Event

• 34: Synchronous with SM 2 event (outputs

available)

UINT16

RW

0x0000 (0

dec

)

1C33:02

Cycle time

as 1C32:02

UINT32

RW

0x000F4240 (1000000

dec

)

1C33:03

Shift time

Time between SYNC0 event and reading of the in-
puts (in ns, only DC mode)

UINT32

RO

0x00000384 (900

dec

)

1C33:04

Sync modes
supported

Supported synchronization modes:

• Bit 0: free run is supported

• Bit 1: synchronous with SM 2 event is

supported (outputs available)

• Bit 1: synchronous with SM 3 event is

supported (no outputs available)

• Bit 2-3 = 01: DC mode is supported

• Bit 4-5 = 01: input shift through local event

(outputs available)

• Bit 4-5 = 10: input shift with SYNC1 event (no

outputs available)

• Bit 14 = 1: dynamic times (measurement

through writing of 1C32:08 or 1C33:08)

UINT16

RO

0x0001 (1

dec

)

1C33:05

Minimum
cycle time

Minimum cycle time (in ns)

UINT32

RO

0x000F4240 (1000000

dec

)

1C33:06

Calc and
copy time

Time between reading of the inputs and availability of
the inputs for the master (in ns, only DC mode)

UINT32

RO

0x00000000 (0

dec

)

1C33:07

Minimum
delay time

UINT32

RO

0x00000384 (900

dec

)

1C33:08

Command

• 0: Measurement of the local cycle time is

stopped

• 1: Measurement of the local cycle time is

started

The entries 1C32:03, 1C32:05, 1C32:06, 1C32:09,
1C33:03, 1C33:06, and 1C33:09 are updated with the
maximum measured values.
For a subsequent measurement the measured values
are reset

UINT16

RW

0x0000 (0

dec

)

1C33:09

Maximum
delay time

Time between SYNC1 event and reading of the in-
puts (in ns, only DC mode)

UINT32

RO

0x00000384 (900

dec

)

1C33:0B

SM event
missed
counter

as 1C32:11

UINT16

RO

0x0000 (0

dec

)

1C33:0C

Cycle ex-
ceeded
counter

as 1C32:12

UINT16

RO

0x0000 (0

dec

)

1C33:0D

Shift too
short
counter

as 1C32:13

UINT16

RO

0x0000 (0

dec

)

1C33:20

Sync error

as 1C32:32

boolean

RO

0x00 (0

dec

)

4.6.2.3

Profile-specific objects (0x6000-0xFFFF)

The profile-specific objects have the same meaning for all EtherCAT slaves that support profile 5001.

EP9214-0023 and EP9224-0023