Comissioning and Configuration

Switch off of the box due to undervoltage

Since undervoltage impairs the function of the safety mechanisms, a warning is given in the process data
from an input voltage of 21.5 V. If the voltage falls below 18 V all outputs are switched off and the Error bit is
set.

Undervoltage is detected independently for Us and Up.

Fig. 43: Undervoltage bits

Note

Switching on again

Switching off due to undervoltage and overtemperature is equivalent to the response of the
current monitoring, but applies to the entire box and all outputs. The error must be reset by
setting the process data GLOBAL RESET or by power off / restart of the module!

Switching load circuits on again after switch-off

This takes place either via the process data [

}

 61] by EtherCAT or by the reset input [

}

 26] directly on the

box.

4.4.3

Setting the current limitation

The switch-off behavior of the individual load circuits can be adapted to the application.

The following modes can be set individually for each channel:

• Very fast acting

• Fast acting

• Slow acting

• Time delay

Release time (switch-off time) of the modes

Rated current

Very fast acting

Fast acting

Slow acting

Time delay

100 %

1 h

-

-

-

110 %

1 h

4 h

-

-

120 %

7 min

4  h

-

-

150 %

30 s

30 min

1 h

4 h

210 %

500 ms

20 sec

20 s

100 s

275 %

500 ms

1 sec

20 s

10 s

300 %

20 ms

100 ms

1 s

3 s

EP9214-0023 and EP9224-0023

42

Version 2.0.0