3 index 6020 dpo inputs ch.3, 4 index 6030 dpo inputs ch.4, 5 index 7000 dpo outputs ch.1 – BECKHOFF EP9214-0023 User Manual

Page 57

Advertising
background image

Comissioning and Configuration

4.5.1.3.3

Index 6020 DPO Inputs Ch.3

Index

Name

Meaning

Data type

Flags

Default

6020:0

DPO Inputs
Ch.3

Input of the first channel

UINT8

RO

0x10 (16

dec

)

6020:01

Error Us

The current monitoring of Us has tripped. The bit must be
reset by a ‘Global Reset’ (F707:04) or by the corresponding
Reset Us (7000:05). The output cannot be activated as
long as the bit is 1.

boolean

RO

0x00 (0

dec

)

6020:02

Error Up

The current monitoring of Up has tripped.

boolean

RO

0x00 (0

dec

)

6020:03

Warning Us

The monitoring has detected overcurrent; the switching off
of output Us on this channel is imminent if the current con-
sumption of the branch does not decrease.

boolean

RO

0x00 (0

dec

)

6020:04

Warning Up

The monitoring has detected overcurrent; the switching off
of output Us on this channel is imminent if the current con-
sumption of the branch does not decrease.

boolean

RO

0x00 (0

dec

)

6020:05

Status Us

0: The output is switched off
1: The output supplies 24 V

boolean

RO

0x00 (0

dec

)

6020:06

Status Up

0: The output is switched off
1: The output supplies 24 V

boolean

RO

0x00 (0

dec

)

6020:07

Channel Error

6020:01 or 6020:02 are set

boolean

RO

0x00 (0

dec

)

6020:0E

Sync error

boolean

RO

0x00 (0

dec

)

6020:0F

TxPDO State

boolean

RO

0x00 (0

dec

)

6020:10

TxPDO Toggle

boolean

RO

0x00 (0

dec

)

4.5.1.3.4

Index 6030 DPO Inputs Ch.4

Index

Name

Meaning

Data type

Flags

Default

6030:0

DPO Inputs
Ch.4

Input of the first channel

UINT8

RO

0x10 (16

dec

)

6030:01

Error Us

The current monitoring of Us has tripped. The bit must be
reset by a ‘Global Reset’ (F707:04) or by the corresponding
Reset Us (7000:05). The output cannot be activated as
long as the bit is 1.

boolean

RO

0x00 (0

dec

)

6030:02

Error Up

The current monitoring of Up has tripped.

boolean

RO

0x00 (0

dec

)

6030:03

Warning Us

The monitoring has detected overcurrent; the switching off
of output Us on this channel is imminent if the current con-
sumption of the branch does not decrease.

boolean

RO

0x00 (0

dec

)

6030:04

Warning Up

The monitoring has detected overcurrent; the switching off
of output Us on this channel is imminent if the current con-
sumption of the branch does not decrease.

boolean

RO

0x00 (0

dec

)

6030:05

Status Us

0: The output is switched off
1: The output supplies 24 V

boolean

RO

0x00 (0

dec

)

6030:06

Status Up

0: The output is switched off
1: The output supplies 24 V

boolean

RO

0x00 (0

dec

)

6030:07

Channel Error

6030:01 or 6030:02 are set

boolean

RO

0x00 (0

dec

)

6030:0E

Sync error

boolean

RO

0x00 (0

dec

)

6030:0F

TxPDO State

boolean

RO

0x00 (0

dec

)

6030:10

TxPDO Toggle

boolean

RO

0x00 (0

dec

)

4.5.1.3.5

Index 7000 DPO Outputs Ch.1

Index

Name

Meaning

Data type

Flags

Default

7000:0

DPO Outputs
Ch.1

UINT8

RO

0x06 (6

dec

)

7000:01

Output Us

0: Us will be switched off
1: Us will be switched on

boolean

RO

0x00 (0

dec

)

7000:02

Output Up

0: Us will be switched off
1: Us will be switched on

boolean

RO

0x00 (0

dec

)

7000:05

Reset Us

An error on Us will be reset

boolean

RO

0x00 (0

dec

)

7000:06

Reset Up

An error on Up will be reset

boolean

RO

0x00 (0

dec

)

EP9214-0023 and EP9224-0023