6 conductor losses, 7 power outputs – BECKHOFF EP9214-0023 User Manual

Page 23

Advertising
background image

Mounting and cabling

Technical data

Technical data

Rated voltage according to IEC 61076-2-101

300 V (according to IEC 61076-2-101)

Contamination level according to IEC 60664-1

3/2 (according to IEC 60664-1)

Insulation resistance IEC 60512-2

>10

9

W

Current carrying capacity according to
IEC 60512-3

16 A at 40°C (according to IEC 60512-3)

Volume resistance according to IEC 60512-2

< 5 mW

Protection class conforms to IEC 60529

IP65/66/67, when screwed together

Permissible ambient temperature

-30°C to +80°C

Material properties

TPE-U (PUR) halogen-free according to DIN VDE 0472
Part 815,
flame-retardant according to cULus 20549

Approbations

UL

Cable outside diameter

7.80 ± 0.20 mm

Bending radius

min. 6 x D (external diameter)

Parameter

Max. speed 5 m/s, max. acceleration 10 m/s²

Number of cycles

At least 10 million cycles with a max. travel path of 20
meters

3.3.6

Conductor losses

In the case of the power cables ZK2030-xxxx-yyy, a total length of 15 m should not be exceeded at 16 A.
When wiring, note that with a rated voltage of 24 V the function of the modules can no longer be guaranteed
from a voltage drop of 6 V. Variations in the output voltage from the power supply unit must also be taken
into account.

Fig. 19: ZK2030-xxxx-yyy - Conductor losses

Alternatively, larger cable cross-section can be used, e.g. 2.5 mm

2

.

3.3.7

Power outputs

The supply voltages are output via four 4-pole M8 sockets in the lower third of the modules (1, 2, 3 and 4).

EP9214-0023 and EP9224-0023